Symptom; system turns on and off more frequently, but runs; Resetting the Thermostat or Thermostat Settings; DÉP ANNA; Réinitialisation du thermostat ou de ses réglages; les boutons de température - Emerson 1F75P-21NP - Manuel d'utilisation - Page 7

Table des matières:
- Page 2 – WIRING; • Do not exceed the specification ratings.; WARNING; Do not use on circuits exceeding specified voltage.; CAUTION; Désignation de la borne; CÂBLAGE; et ils décrivent les fonctions des bornes du thermostat.; INSTALLA; Précautions; Une; A VER; l’installation soit terminée.
- Page 3 – INSTALLER MENU; will not be displayed in AC mode.; MENU DE L ’IN; seconde; d’installateur; C ou HP; sera; HP; – Pompe à chaleur ou; AC; – Climatiseur; situé à l’arrière du thermostat. Modifiez l’; ) Sélecteur de borne; ). Si la thermopompe installée exige qu’une borne; Cool
- Page 4 – DO NOT operate the cooling system.; TEST EQUIPMENT; ° above room temperature. The auxiliary heat; Heat On Auxiliary; . When compressor lockout is turned ON; MISE EN GARDE; MISE À L; Système de chauffage; (chauffage en marche; . Lorsque le verrouillage du compresseur
- Page 5 – THERMOSTAT OVERVIEW; the location/operation of the thermostat buttons and switches.; THERMOSTAT BUTTONS; SEE TROUBLESHOOTING; USING THE THERMOSTAT; APERÇU; Avant d’utiliser le thermostat, vous de; UTILISATION
- Page 6 – Misconfiguration between menu; TROUBLESHOOTING; Problème; DÉP
- Page 7 – Symptom; system turns on and off more frequently, but runs; Resetting the Thermostat or Thermostat Settings; DÉP ANNA; Réinitialisation du thermostat ou de ses réglages; les boutons de température
Problème
Cause possible
Mesure corrective
La cadence de
l’appareil de
chauffage (ou du
climatiseur) est
trop rapide ou trop
lente (variation de
température trop
grande ou trop
restreinte) /
Pas de chaleur de
première étape
L ’emplacement du thermostat et la taille
du système de chauffage peuvent affecter
la durée du cycle.
Les thermostats numériques offrent un contrôle
précis et un cycle plus rapide que les anciens modèles
mécaniques. Le système se met en marche et à
l’arrêt plus fréquemment, mais il fonctionne moins
longtemps. Pour
ac
croître la durée des cycles,
sélectionnez SL
O, pour cycle lent, dans
le menu de
l’installateur. (V
oir les articles du menu
30 et 35
.)
Si une durée de cycle acceptable ne peut pas être
atteinte, contactez un technicien en CV
C local pour
des suggestions supplémentaires.
Assurez-vous que
l’élément de menu
20
et le fil du cavalier correspondent.
L ’icône «
Call for
Service » (Appeler
le technicien)
apparaît
1.)
Le système de chauffage n’est pas
en mesure de chauffer l’espace à
10
degrés près du point de consigne
dans les
2
heures
2.)
Le système de climatisation n’est
pas en mesure
de refro
idir l’espace
à
10
degrés près du point de consigne
dans les
2
heures
3.)
Si «
--
» est affiché au lieu de la
température de la pièce, il faut
remplacer le thermostat
4.)
Aucun des boutons ne fonctionne
sur le thermostat
5.)
Si «
Call for
Service » (Appeler
le technicien) clignote,
l’auto-diagnostic du compresseur a
détecté un problème avec l’appareil
extérieur
1.)
Voir la mesure corrective pour «
Pas de
chauffage »
2.)
V
oir la mesure corrective pour « Pas de
climatisation »
3.)
Remplacez le thermostat
4.)
R
echercher un bouton bloqué
5.)
Communiquez avec un technicien pour vérifier
que l’équipement fonctionne bien
7
7
TROUBLESHOOTING (C0ntinued)
Symptom
Possible Cause
Corrective Action
Furnace (Air
Conditioner)
Cycles Too Fast or
Slow (narrow or
wide temperature
swing) /
No First Stage
Heat
The location of the thermostat and/or
the size of the Heating System may be
influencing the cycle rate
Digital thermostats provide precise control and
cycle faster than older mechanical models. The
system turns on and off more frequently, but runs
for a shorter time. If you would like to increase
cycle time, choose SLO for slow cycle in the
Installer menu. (Reference menu items
30 & 35
) If
an acceptable cycle rate is not achieved, contact
your HVAC service person.
“Call for Service”
icon appears on
displayed
1.)
Heating system is not able to heat
the space to within
10
degrees of
the setpoint within
2
hours
2.)
Cooling system is not able to cool
the space to within
10
degrees of
the setpoint within
2
hours
3.)
If “--” is displayed for the Room
Temperature, a replacement
thermostat is needed
4.)
None of the buttons operate on
the thermostat
5.)
If “Call for Service” is flashing,
compressor self diagnostic is
detecting an issue with the
outdoor unit
1.)
See corrective action for “No Heat”
2.)
See corrective action for “No Cool”
3.)
Replace thermostat
4.)
Check for a stuck button
5.)
Contact a service person to verify the
equipment is operating correctly
WARNING:
This product contains a chemical known to the state of California to cause
cancer and birth defects and other reproductive harm.
Resetting the Thermostat or Thermostat Settings
To conveniently reset only the user settings back to factory defaults, press the temperature
and
buttons and move the system switch from OFF to HEAT at the same time
and hold until
the display goes blank and resets.
DÉP ANNA
GE (suite)
Réinitialisation du thermostat ou de ses réglages
Pour ne réinitialiser que les réglages à leur statut par défaut, appuyez simultanément sur
les boutons de température
ou
, et réglez le sélecteur système de OF
F à HEAT, tous à la
fois, et gardez-les enfoncés jusqu’
à ce que l’affichage s’
efface et se réinitialise.
NOTE:
This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to part
15
of the FCC Rules. These limits
are designed to provide reasonable protection againts harmful interference
in a residential installation. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no gurantee that interference will not occur in a partiduclar installation. If
this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the following
measures:
• Reorient or relocate the receiving antenna
• Increase the separation between the equipment and receiver
•
Connect the equipment into an outlet on a circuit different from that to which
the receiver is connected
• Consult the dealer or an experienced radio/TV technician for help
CAN ICES-003 (B) / NMB-003 (B)
„Téléchargement du manuel“ signifie que vous devez attendre que le fichier soit complètement chargé avant de pouvoir le lire en ligne. Certains manuels sont très volumineux, et le temps de chargement dépend de la vitesse de votre connexion Internet.
Résumé
2 Terminal Designations Terminal Function GL Low Speed Fan Relay R Power ( 24 V) O/B Changeover Terminal-Energized in Cool (O) or Heat (B) for Heat Pump. Y Heat and Cool Mode 1 st Stage Compressor GH High Speed Fan Relay W Heat Mode – 2 nd stage (Electric) C Common wire for 24V WIRING Refer to equi...
1 câble de raccordement Installer’s Menu # (Hold Menu 3 Seconds) Description Default Setting (flashing icons) Settings ( Press or ) 20 Algorithm – AC or HP (If HP is selected, item # 32 will be displayed) HP HP – Heat Pump or AC – Air Cond. 30 Heat Cycle Rate (how often the heat will turn on)...
4 CAUTION ! To prevent compressor and/or property damage, if the outdoor temperature is below 50° F, DO NOT operate the cooling system. Do not allow the compressor to run unless the compressor oil heaters have been operational for 6 hours and the system has not been operational for at least 5 minute...